Grafik: Logo Franzen Feuerschutztüren
Franzen Feuerschutztüren GmbH
Gerhard-Welter-Str. 7
D-41812 Erkelenz

phone +49 (0) 2431-80070

Franzen fire door

Single leaf fire door T90 TSN-11

Franzen fire resistance door T90 TSN-11 "System Schröders"
Single-leaf hinged steel fire-resistant door
Fire resistance

T90
Allgemeine bauaufsichtliche Zulassung Nr. Z 6.20-1937, DIBt Berlin

Combinable with additional performance characteristics:

Smoke control
(optional)

Smoke control according to DIN 18095 RS-1
Allgemeine bauaufsichtliche Zulassung Nr. Z 6.20-1909, DIBt Berlin

Burglar resistance
(optional)

RC4 - classification report no. 22-5/15.119, PIV-Velbert
RC3 - classification report no. 22-4/15.117, PIV-Velbert
RC2 - classification report no. 45-47/22, PIV-Velbert
RC1 - classification report no. 212 24294, ift Rosenheim

according to DIN EN 1627 ff

Acoustic performance
(optional)

up to RW (C;Ctr) = 53 (-1;-5) dB

according to EN ISO 10140-1 / EN ISO 10140-2 / EN ISO 717

proof of airborne sound insulation for security doors
(measurement reports, test reports, expert opinions)

Thermal transmittance

UD-value ≥ 1.6 W/(m²K) according to EN ISO 10077-1

Air tightness
(optional)

up to class 4 according to EN 12207 (up to 600 Pa)

expert opinion no. 11-000082-PR01
Resistance to positive and negative pressure
(optional)

up to 5.000 Pa according to DIN EN 12211

expert opinion no. 16-003037-PR01
Flush with surface
(optional)

flush-mounted design FLAT

Explosion protection
(optional)
Logo ATEX For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for Franzen hinged doors (in German language) System Schröders (PDF)
Technical data
Dimensions
(rough building dimension)
width from 625 mm up to 1,500 mm
height from 1,750 mm up to 3,250 mm
Dimensions flap
(rough building dimension)
width from 625 mm up to 660 mm
height from 660 mm up to 1,750 mm
Door leaf

leaf thickness 68 mm to 69 mm - smooth double-walled
plate thickness 1.0 mm to 1.5 mm

  • thin rebate design
    • optional thick rebate design
    • insulating insert
      • optional insulation inlet full-face glued and pressed with cover plate
        thus particularly plane and smooth door leaf
Frame
  • frame-system "ZNG" with flush clipped in Thelesol® fire protection strips
  • (see installation variants)
  • corner frame
  • optional enclosing frame
  • optional block frame

with elastic rubber seal
(seal type depending on performance characteristic)

Floor seal

required for smoke control, acoustic performance, air tightness

  • optional lowerable floor seal or
  • sliding seal
Glass inset
(optional)

glass dimensions and -form variable
(rectangular glass inset max. 1,130 x 2,850 mm)

minimum frieze width: 130 mm

  • optional with intermediate glass inset bars
  • optional with port-hole (ø approx. 450 mm clear view)

glass inset bars with concealed screw connection (for rectangular glass inset)

Hinges

2/3-part KO door hinges
with patented easy-running bearings as easy running doors

  • optional door hinge with 3D adjustment
Fittings
  • optional any approved handle set according to EN 1906 resp. EN 179
  • optional panic bar handle or push bar according to EN 1125

for RC version: protective fitting DIN 18 257

Locking

single locking according to EN 12209, depending on version multi-point locking
profile cylinder prepared (cylinder on-site)
securing pins

  • for version RC4: lock combination with triple locking
  • optional panic locking
Self-closing

door closer according to DIN EN 1154

  • optional spring hinge for smaller doors / flaps
  • optional hold-open system according to DIN EN 14637
Installation
  • in masonry(thk ≥ 175 mm)
  • in concrete(thk ≥ 140 mm)
  • in aerated concrete(thk ≥ 150 mm)
  • in mounting walls min. F90 (thk ≥ 100 mm)
  • in encased steel columns(thk ≥ 140 mm)
  • optional blunt installation in soffit
  • optional installation on the wall plate
  • approved for installation at great heights (installation not at floor level: height on one or both sides > 500 mm above ground level - e.g. as manhole door/flap) with lower fire and smoke seal - also thresholdless
Marking

mark of conformity - "Ü"
according to German conformity mark regulation

Optional
  • lock control
  • automated opening
  • motor locks ( also in 3-way locking)
  • powder coating in RAL colors
  • prison cell doors (special locking and food flap)
  • special solutions according to request and customer requirements